topnav.gif
 
   
   
 
 

 

TCPRK-BBU SERIES

 
Other Products

 

 

RUGGED DC UPS

- RACK MOUNT DC UPS
- RUGGED MILITARY DC UPS
- rUGGED COTS DC UPS
- CUSTOM DC UPS POWER SYSTEM




Shown with the cover removed

Technology Dynamics offers a full array of Rugged DC UPS Systems to suit any commercial, industrial, or military application, including those that require DC UPS's which can withstand Military Environmental and Electrical Standards such as MIL-STD-810, MIL-STD-167, MIL-STD-1399, MIL-STD-461, and more. These Rugged UPS Systems are available in rack mount, panel mount and custom configurations to suit applications with tight space constraints.

Any Standard input voltage (single or three phase) can be accommodated, in 50, 60, or 400 Hz frequencies, changing a given input voltage and frequency to a DC output voltage with battery configurations designed to meet your load and reliable performance, as well as the resulting MTTR, high MTBF, and Cost-To-Own figures.

 

 
STANDARD SINGLE OUTPUT DC POWER SUPPLY

As standard we have available our TCPRK series with very short cycle availability for Battery Backup Applications.


The TCPRK Series satisfies an emerging market where "critical" continuous power is required. Designed as a complete system with power supply, charger and board batteries, loaded with standard features the TCPRK-BBU Series is ideal for medical, industrial and communication applications.



400 WATTS
600 WATTS
1000 WATTS
Model
Nominal Voltage
(VDC)
Maximum Current
(ADC)
Model
Maximum
Current
(ADC)
Model
Maximum
Current
(ADC)
TCPRK-BBU-5-60
3.3/5V
60A
TCPRK-BBU-5-80
80A
Consult Factory
TCPRK-BBU-12-34
12V
34A
TCPRK-BBU-12-50
50A
TCPRK-BBU-15-27
15V
27A
TCPRK-BBU-15-40
40A
TCPRK-BBU-24-17
24V
17A
TCPRK-BBU-24-25
25A
TCPRK-BBU-24-41
41A
TCPRK-BBU-36-11
36V
11A
TCPRK-BBU-36-16
16A
Consult Factory
TCPRK-BBU-48-8
48V
8A
TCPRK-BBU-48-12
12A
TCPRK-BBU-48-20
20A

NOTE: OTHER RACK SIZES AVAILABLE DEPENDING ON POWER LEVES AND BATTERY SIZE



OPTION DESIGNATION SUFFIX CODE
LOW VOLTAGE BATTERY DISCONNECT
The LVBD module adds a new dimension to battery backup power supplies. The power supply simultaneously charges the battery and powers the load. If the AC power fails the battery continues to support the load. However, when the battery voltage drops below a predetermined level, the LVBD module disconnects the battery from the load, thereby protecting the battery from the damaging effects of complete discharge.
AUTO LINE SELECT -ALS
POWER FACTOR CORRECTION -PFC
REDUNDANT OPERATION -ORD
FORCED CURRENT SHARING -FCS
RUGGED/MILITARIZED -MIL
HOT PLUGABBLE -HSP
MS CONNECTOR -MSC
WIDE TEMP OPERATION -WTD


  • Compact, light weight
  • Rugged constreuction
  • OV/OL/OT Protected
  • Built-In On Board batteries
  • Input and battery circuit breakers
  • Voltage & Current Meters
  • Visual and electronic signals
  • Low voltage battery disconnect

  • Redundant Operation (N+1)
  • Forced Current Sharing
  • Low Voltage Battery Disconnect
    (LVBD) for battery back-up operation
    .
  • Wide temperature range
  • Auto line selection
  • Power Factor Correction
  • Ruggedized
 



ELECTRICAL:

AC Input Voltage : 90-132/180-264 VAC Standard, Auto-Line Selection optional.
AC Input Frequency: 47-63Hz Standard, 47-400Hz optional
Regulation: Line ± .3%
Load + 2%
Ripple: 1% peak to peak, not to
exceed 100mVpp
Efficiency: 85% typical
Output voltage adj: +10% on main output
Overvoltage Protection: Set at 120% of main output, automatic recovery
Overload Protection: Current limiting, automatic recovery




Operating Temperature:
0°C to + 50°C standard
-40°C to 75°C optional
Storage Temperature: -40°C to 85°C
Cooling: Internal ball bearing DC fan
Safety: meets UL 1950, CSA 1402 A
EMI: meets FCC Class A
Humidity: 90% non condensing
Size: 3.5" (H) x 19" (W) x18" (D)
Weight: Approx: 25lbs (depending on battery type & size)

 
 

 

Technology Dynamics