topnav.gif
 
   
 
 

 

NTDM - 4HS SERIES



Other Products

 

 

HOT SWAP

1500 - 12000W
6U HIGH (N+1) REDUNDANT
SINGLE OUTPUT RACK MOUNT POWER SYSTEM



The NTDM-4HS Series of Hot Swap Rack systems offer (N+1) redundant or high power paralleled outputs of 4 modules per enclosure. This series is especially suitable for critical telecom and wireless systems.

1500 WATT MODULE
NORMAL VOLTAGE
(VDC)
MAXIMUM
CURRENT
(ADC)
MODEL
12V 125 NTDM-4HS-12-125
15V 100 NTDM-4HS-15-100
24V 62 NTDM-4HS-24-62
28V 54 NTDM-4HS-28-54
48V 31 NTDM-4HS-48-31
110V 14 NTDM-4HS-110-14
2000 WATT OUTPUT
NORMAL VOLTAGE
(VDC)
MAXIMUM
CURRENT
(ADC)
MODEL
12V CONSULT FACTORY
15V
24V 84 NTDM-4HS-24-84
28V 72 NTDM-4HS-28-72
48V 42 NTDM-4HS-48-42
110V 18 NTDM-4HS-110-18
3000 WATT OUTPUT
NORMAL VOLTAGE
(VDC)
MAXIMUM
CURRENT
(ADC)
MODEL
12V CONSULT FACTORY
15V
24V 125 NTDM-4HS-24-125
28V 107 NTDM-4HS-28-107
48V 62 NTDM-4HS-48-62
110V 27 NTDM-4HS-110-27
 

(Example) Parallel OperationModel: NTDM-4HS-28-54

4 Each 1500 Watt modules in parallel providing a total of 6000 Watts.

(Example) Redundant Operation (N+1)

Model: NTDM-4HS-28-107 ORD: 4 Each 3000 Watt modules all units operating providing a total of 12,000 Watts. Should one fail the other units continue to provide the load of 9000 Watts.

OPTION DESIGNATIONS
SUFFIX CODE
Low Battery Voltage Disconnect (LVBD): The LVBD Module adds a new dimension to battery backup power supplies. The power supply simultaneously charges the battery and powers the load. If input power fails, the battery continues to support the load. However, when the battery voltage drops below a predetermined level, the LVBD module disconnects the battery from the load, thereby protecting the battery from the damaging effects of complete discharge.
RUGGEDIZED/MILITARIZED
-MIL
BATTERY BACK-UP
-LVBD
POWER FACTOR CORRECTION
-PFC
3 PHASE INPUT
-3PH
IEEE 488 PORT
-IEEE
400 HZ OPERATION
-4HZ
23" WIDE TELECOM RACK
-23RK

  • Sturdy fold down handle
  • Circular input connector MS-3102
  • Remote sensing post isolation diodes
  • Floating connectors for hot swap insertion
  • OV/OL/OT protection main output
  • Circuit breaker input
  • Equipped with isolation diodes for redundancy/parallel operation
  • Tightly regulated.
    LED indicators (each module)
  • Output power good Input power good LED
  • MTBF > 150,000 hours.11” high 19” rack enclosure

  • 3 Phase input
  • 400 Hz operation
  • IEEE 488 communications port
  • 23" Wide Telecom Rack
  • Meters
  • Power factor correction
  • Low Voltage Battery Disconnect. (LVBD) for battery back-up operation
  • Militarized version: Mil-STD-810



 



ELECTRICAL:

Input: (1500W) 85-132 - 175-265VAC, 47-63 Hz (2000-3000W) 220VAC 1 Phase or 115/208 3 Phase
Regulation: 2%+Load .3%+Line
Ripple: 1% peak to peak, not to exceed 200mV
Efficiency: 80% typical.
Hold up Time: 20ms min.
In Rush Current: 60A max ½ cycle / module
Protections: OV, OL & OT





Operating Temperature: 0ºC to + 50ºC Standard -40ºC to +60ºC optional
Storage Temperature: -40ºC +85ºC
Cooling: Internal DC fan
Weight: Modules (15 lbs) each, Rack (24.5 lbs)
Size: 11”(H) x 19” Std Rack (W) x 16.25” (L)

.

 
 

 