topnav.gif
 
   
   
 
 

 


T1U-HS MODEL


Other Products

 

 

HOT SWAP
600W - 1200W

1U HIGH N+1 REDUNDANT
SINGLE OUTPUT RACK MOUNT
POWER SYSTEM


The T1U 600 Series is a three module redundant hot swap system intended for telecom, IT equipment as well as monitoring and control application. It can be easily equipped with an LVBD* module to form a DC UPS system when backup batteries are available.



SINGLE MODULE
MODEL
OUTPUT
VOLTAGE
CURRENT(A)
MAX/MODULE

CURRENT(A)
MIN.

REGULATION
RIPPLE
VOLTAGE ADJ.
RANGE

2 MODULE
(N+1)

3 MODULE
(N+1)
T1U 600-12
12V
50A
0A
1%
<1%
>±5%
600W
1200W
T1U 600-15
15V
40A
0A
1%
<1%
>±5%
600W
1200W
T1U 600-24
24V
25A
0A
1%
<1%
>±5%
600W
1200W
T1U 600-28
28V
21A
0A
1%
<1%
>±5%
600W
1200W
T1U 600-48
48V
12.5A
0A
1%
<1%
>±5%
600W
1200W


  • (N+1) Redundant with Orings diodes.
  • Active current sharing.
  • Active power factor correction.
  • Universal Input 85-265 VAC.
  • High efficiency.
  • Full protection OVP, OCP & OTP
  • Isolation class 1>3000 VAC. Primary - secondary 1500V, Primary to GND.
  • OV/OL/OT Protection Main Output
  • Remote sense.
  • Power Good Signal.

  • Wide Temperature Range -20°C to + 70°C with derating
  • Militarized / Ruggedized to meet MIL-STD-810
  • LVBD*: Low Voltage Battery Disconnect for battery back-up operation (see below for details)

    *Low Battery Voltage Disconnect (LVBD): The LVBD Module adds a new dimension to battery backup power supplies. The power supply simultaneously charges the battery and powers the load. If input power fails, the battery continues to support the load. However, when the battery voltage drops below a predetermined level, the LVBD module disconnects the battery from the load, thereby protecting the battery from the damaging effects of complete discharge.

 

ELECTRICAL:

AC input voltage: 85-265VAC full range
Input Frequency: 50-60 Hz
Efficiency: 86% at full load.
Line Regulation: +.5%
Load Regulation: +2%
Ripple & Noise: 1% peak to peak, not to exceed 300mVpp.
Protections: OV, OL, & OT
Hold-up time: 16mS @ 600W output




Operating temperature: -0°C to +50°C
Storage temperature: -40°C to +85°C
Cooling: Internal DC fan per module
Size: 1.75" (H) x 19" (W) x 17.75" (L)
Weight: 4lbs. / Modules 20 lbs. per Rack.

 
 

 

Technology Dynamics