TDL- HS SERIES
|
|
Other Products
|
|
|
pDF Downloads
|
|
 |
|
|
hOT SWAP |
 |
1000
- 3000W
3U hIGH (N+1) REDUNDANT
SINGLE / MULTIPLE OUTPUT
RACK MOUNT POWER SYSTEM |
The low-cost TDL-HS Series of Hot
Swap Rack Systems offers low height,
(N+1) redundant configurations of
2 or 3 modules per enclosure. This
series is especially suitable for
critical telecommunication systems,
computer systems, and COTS military
applications.
|
|
 |
|
SINGLE
/ MAIN OUTPUT (3 MODULES)
| 5/3.3 |
125 |
TDL-HS-5-125 |
| 12 |
100 |
TDL-HS-12-100 |
| 24 |
85 |
TDL-HS-24-85 |
| 28 |
75 |
TDL-HS-28-75 |
| 48 |
22 |
TDL-HS-48-22 |
MULTIPLE
OUTPUT
| -5V@6A |
A1 |
| -12V@6A |
A2 |
| -15V@6A |
A3 |
| -24V@3A |
A4 |
| -5V@10A |
B1 |
| +12V@10A |
B2 |
| +15V@10A |
B3 |
| +24V@3A |
B4 |
| 5V@6A |
C1 |
| 12V@6A |
C2 |
| 15V@6A |
C3 |
| 24V@6A |
C4 |
| 5V@20A |
D1 |
| 12V@16A |
D2 |
| 15V@14A |
D3 |
| 24V@9A |
D4 |
| 5V@20A |
E1 |
| 12V@16A |
E2 |
| 15V@14A |
E3 |
| -24V@9A |
E4 |
** Other models
available. Please consult factory for details.
|

- 3U (5.25")
High, 19" Wide Rack-Mount Enclosure
- 1 to 6 Outputs
- MTBF >150,000
Hours
- LED Indicators
(each module): Output Power (good) Input
Power (good)
- All outputs
tightly regulated
- All outputs
equipped with Isolation diodes for redundancy
- Forced Current
Sharing
- OV Protection
Main Output
- Floating
connectors for hot-swap insertion
- Remote
Sensing post isolation diodes

- ORD:
Wide Temperature Option
- MIL: Militarized
/ Ruggedized to meet MIL-STD-810
- LVBD*: Low
Voltage Battery Disconnect for battery
back-up operation (see below for details)
- Main Output only
- UPS:
Battery Backup (All Outputs)
*Low Battery Voltage Disconnect (LVBD):
The LVBD Module adds a new dimension
to battery backup power supplies. The
power supply simultaneously charges
the battery and powers the load. If
input power fails, the battery continues
to support the load. However, when the
battery voltage drops below a predetermined
level, the LVBD module disconnects the
battery from the load, thereby protecting
the battery from the damaging effects
of complete discharge.
|
|

ELECTRICAL:
AC input voltage:
110/230 VAC Auto Select
Input Frequency: 47-63
Hz
Efficiency: 80% typical
for Single-Output units, 70% typical for
4 multiple outputs units
Line Regulation: +.3%
Load Regulation: +2%
Ripple & Noise: 1%
peak to peak, not to exceed 100mV
Protections: OV, OL, &
OT
Hold-up time: 20ms minimum
In-Rush Current: 60A Max
1/2 cycle
Operating temperature:
-0°C to +50°C standard, -30°C
to +60°C optional
Storage temperature: -30°C
to +85°C
Cooling: Internal
ball bearing DC fan
Size: 5.25" (H) x
19" (W) x 17.9 (L)
Weight: 25 Lbs. (11.3 kg)
for 3 Module System |
|

|
|