topnav.gif
 
   
   
 
 

 

TCP SERIES

 


Other Products

 

aC - DC POWER SUPPLY
SINGLE OUTPUT
1,200-1,500 WATTS

 



The TCP-IK family of DC output power supplies is designed to satisfy a market for low cost, high reliability
applications. The TCP is especially suitable for
critical systems in remote locations, severe
environment, redundant (N+1) or battery back-up
uninterruptable operation. This versatile design is loaded with options, making it particularly suitable for standard, modified & custom telecommunication applications.


1200 WATTS

1200 MODEL
VOLTAGE
AMPS
TOLERANCE
R&N
EFFICIENCY
TCP-1K2-3.3
3.3V
200A
±2%
2%
77%
TCP-1K2-05
5V
200A
±2%
2%
77%
TCP-1K2-12
12V
100A
±1%
1%
83%
TCP-1K2-15
15V
80A
±1%
1%
85%
TCP-1K2-24
24
50A
±1%
1%
87%
TCP-1K2-48
48V
25A
±1%
1%
90%



1500 WATTS

1500 MODEL
VOLTAGE
AMPS
TOLERANCE
R&N
EFFICIENCY
TCP-1K5-12
12V
125A
±1%
1%
83%
TCP-1K5-15
15V
100A
±1%
1%
84%
TCP-1K5-24
24V
62.5A
±1%
1%
85%
TCP-1K5-48
48V
32A
±1%
1%
87%


OPTION DESIGNATION SUFFIX CODE
LOW VOLTAGE BATTERY DISCONNECT
The LVBD module adds a new dimension to battery backup power supplies. The power supply simultaneously charges the battery and powers the load. If the AC power fails the battery continues to support the load. However, when the battery voltage drops below a predetermined level, the LVBD module disconnects the battery from the load, thereby protecting the battery from the damaging effects of complete discharge.
AUTO LINE SELECT -ALS
POWER FACTOR CORRECTION -PFC
REDUNDANT OPERATION -ORD
FORCED CURRENT SHARING -FCS
RUGGED/MILITARIZED -MIL
HOT PLUGABBLE -HSP
BATTERY BACK-UP -LVBD

  • Compact, light weight
  • Tightly regulated output
  • OV/OL/OT protected
  • +5% output adjustment
  • LED indicator
  • Output power good
  • Remote inhibit
  • Input via terminal block
  • MTBF >150,000 hours
  • Meets FCC Docket 20780
  • Level A and VDE 0871/6.78
  • Level A
  • UL1950, CSA, 22.2
  • Meets NEBS

  • Auto Line Selection (90-264 VAC)
  • Redundant Operation (N+1)
  • Ruggedized for Severe Environment
 

ELECTRICAL:

Input: 110/220 VAC 47-400 Hz
Regulation: Line + .1%, Load +1%
Ripple: 1% peak to peak, not to exceed 100mV
Efficiency: 80% typical
Hold up Time: 16ms min.
In Rush Current: 40A max + cycle
Protections: OV, OL & OT



Operating Temperature:
0°C to + 50°C standard
-30°C to 60° optional
Storage Temperature: -40°C to 85°C
Size: 11.5"(L)x5.25"(W)x5.2(H)
Cooling: Internal DC fans
Weight: 13 lb (3kg) max.

 
 

 

Technology Dynamics